SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

He M, Zhang G, Hu S, Liu Y. China Saf. Sci. J. 2019; 29(11): 39-44.

Copyright

(Copyright © 2019, China Occupational Safety and Health Association, Publisher Gai Xue bao)

DOI

10.16265/j.cnki.issn1003-3033.2019.11.007

PMID

unavailable

Abstract

In order to improve fire extinguishing efficiency of water mist, its cooling effect on flame is studied. Firstly, a motion, heat and mass transfer model of water mist in flame areas were established which was utilized to evaluate factors that affected its penetration distance and vaporization performance comprehensively. Then, a method to reasonably identify initial size and velocity of droplets and a co-flow jet water mist system which could improve utilization efficiency were proposed.The results show that those factors rank according to their influence degree from high to low is initial size of droplets, heat transfer temperature difference, initial velocity of droplets, flame plume velocity. Penetration distance and vaporization rate of water mist can be significantly improved by this system. © 2019 China Safety Science Journal. All rights reserved.


Language: zh

NEW SEARCH


All SafetyLit records are available for automatic download to Zotero & Mendeley