SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Zhang W, Zhang Y, Li C, Yuan D. China Saf. Sci. J. 2020; 30(6): 135-141.

Copyright

(Copyright © 2020, China Occupational Safety and Health Association, Publisher Gai Xue bao)

DOI

10.16265/j.cnki.issn1003-3033.2020.06.020

PMID

unavailable

Abstract

In order to explore effects of different restricted forms on flow field of fire plume, fine thermocouple and PIV technologies were used to monitor fire plume's height, temperature and flow field of diffusion burner in free space, side wall space and corner space, and then flow field characteristics in different restricted forms were studied. The experimental results show that when dimensionless source power Q∗ is less than 1. 5, dimensionless flame height Lf / D increases linearly which will become steady approximately when Q∗ exceeds 1. 5. Lateral velocity in different restricted spaces all conform to approximate Gaussian distributions, and sidewall space and corner space cause a certain deviation of flame center. Vortex diameter is between 3. 5 and 8 cm at Q∗ is 1. 982, and its size gradually increase along with increase of side wall surface because vortex will fall off, which will release a lot of heat in a short time and exerts a stretching impact on fire plume. As a result, combustion reaction of fire is promoted, and then a larger vortex is generated. © 2020 China Safety Science Journal


Language: zh

NEW SEARCH


All SafetyLit records are available for automatic download to Zotero & Mendeley
Print