SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Ge F, Qiu T, Zhang M, Ji J. Fire Safety J. 2023; 136: e103732.

Copyright

(Copyright © 2023, Elsevier Publishing)

DOI

10.1016/j.firesaf.2022.103732

PMID

unavailable

Abstract

The objective of this paper is to study the thermal characteristic of low-voltage alternating current (AC) arc faults. Two series of experiments were designed, including polyvinyl chloride (PVC) wire ignitions experiments and electrode arcing experiments (non-ignitions) subjected to arc faults at different effective currents. The ignition time of the wire and the temperature of the electrode were investigated to characterize the arcing hazard.

RESULTS show that the ignition time of the wire decreases with the increasing arc current, and the wire with a larger cross-section area requires more time to be ignited at the same current. For non-ignition experiments, the electrode temperature increases first and then varies little. A heat equilibrium stage can be reached, where the heat transfer of the arc to the electrode is equal to the heat dissipation of the electrode. Furthermore, a heat transfer model for the arc fault is established to obtain the electrode temperature. The temperature of the arc-electrode interface is used to characterize the arc energy, and it is found the temperature showed a logarithmic increase with the current. The results of this study may be useful in the safety design of electrical wires, and can be exploited as hazard indicators for the risk assessment of electrical fires.


Language: en

Keywords

Arc faults; Electrical fires; Low-voltage circuit; PVC coated wire; Thermal characteristic