Lambert K, Welch S, Merci B. Fire Technol. 2018; 54(3): 625-647.

Copyright

(Copyright © 2018, Holtzbrinck Springer Nature Publishing Group)

DOI

10.1007/s10694-018-0700-8

PMID

unavailable

Abstract

Positive pressure ventilation (PPV) fans are widely used by the fire service during firefighting operations in buildings. Fans are positioned to create a flow through the enclosure. This flow can remove the smoke after the fire or affect the direction of the smoke to support firefighting operations. In subway stations, it is less common to use PPV fans. Here, 106 full-scale tests with up to four fans have been performed in a training building that represents a subway station. The fans were used as extraction fans. The generated flow through the subway station has been measured. The critical velocity for a hypothetical tunnel (W × H: 3.17 × 4.15 m) attached to the subway station has been calculated as 2.37 m/s. Reaching the critical velocity has been used as criterion for 'success'. All combinations with four fans exceed this velocity, supporting the idea that the fans could be used to facilitate a firefighting operation. The location of the fans was varied. Combinations with three fans on the platform and one at the top of the staircase performed better than combinations with two fans on the platform, one on the landing and one at the top of the staircase. There is an optimum value for the distance between the fans on the platform and the first step of the staircase. This value depends on the angle of inclination of the fans. The fans were not capable of creating a flow that exceeded the critical velocity in the station itself (L × W × H: 60 × 7.15 × 4.53 m). However, a velocity of 2.40 m/s corresponds to a flow rate that will limit the backlayering distance in the station to 15 m. This was only achieved by tests with four fans (three on the platform and one at the top of the staircase).


Language: en

Keywords

Fire service intervention; Full-scale experiments; Positive pressure ventilation; PPV; Subway stations

NEW SEARCH


All SafetyLit records are available for automatic download to Zotero & Mendeley
Print