White RH, Dietenberger MA, Tran H, Grexa O, Richardson L, Sumathipala B, Janssens M. Fire Mater. 1999; 23(3): 139-146.

Copyright

(Copyright © 1999, John Wiley and Sons)

DOI

unavailable

PMID

unavailable

Abstract

As part of international efforts to evaluate alternative reaction-to-fire tests, several series of room/corner tests have been conducted. Materials tested were mostly different wood products but included gypsum board and a few foam plastics. This is a review of the overall results of related studies in which the different test protocols for the standard room/corner test were used, Differences in the test protocols involved two options for the ignition burner scenario and whether or not the ceiling was also lined with the test materials. The test materials were placed on three walls of the room in all the tests. The two burner scenarios were (1) 40 kW for 300 s followed by 160 kW for 300 s and (2) 100 kW for 600 s and 300 kW for 600 s. The 40 and 160 kW burner scenario without the ceiling lined did not provide a severe enough test for flashover to occur with fire-retardant-treated materials. Use of the 100 and 300 kW burner scenario without lining the ceiling provided the ability to differentiate between wood products with ASTM E 84 flame spread indexes of 70 to 125 and those with higher flame spread indexes. Lining the ceiling with test material creates a more severe test.