Urbas J. Fire Mater. 2002; 26(1): 29-35.

Copyright

(Copyright © 2002, John Wiley and Sons)

DOI

unavailable

PMID

unavailable

Abstract

In the spring of 1997, seven companies and industry associations from the USA and Canada decided to sponsor the cone calorimeter interlaboratory test programme. Reproducibility and repeatability were determined for the scalar variables measured in the cone calorimeter (ASTM E1354) according to the protocol developed by the Board for the Coordination of the Model Codes. The main requirement of the protocol was that the sample irradiance should be 75 kW/m(2). The purpose of the project was to assist the model building code organizations, NFPA and various other groups in the development of a system to determine degrees of combustibility of building materials. Three US and one Canadian laboratory agreed to conduct tests on 16 materials. The results of this round robin show that the cone calorimeter, following the Board for the Coordination of the Model Codes protocol, can provide precision similar to that cited in the current cone calorimeter standards. It is recommended that further improvements of the standards are pursued and provisions are made to improve the quality of operation of the cone calorimeter in commercial laboratories to maintain and possibly improve its repeatability and reproducibility.