SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Chow WK, Wong WK. J. Fire Sci. 1993; 11(4): 329-349.

Copyright

(Copyright © 1993, SAGE Publishing)

DOI

unavailable

PMID

unavailable

Abstract

Whether a smoke extraction system has to be installed for an atrium building in Hong Kong is determined by its volume. This article reports an evaluation of this regulation using the zone model FIRST developed at the Building and Fire Research Laboratory, NIST, U.S.A. A survey of the geometrical configurations of the local atria is made. The general shapes of the atria are classified into three types: 1, 2 and 3, with types 2 and 3 further divided into three sub-types: A, B and C. Smoke filling in those atria is simulated by the model FIRST with the volumes of the atrium space varied from 2500 m3 to 35,000 m3. It is illustrated that specifying only the volume of the atrium space is not good enough to determine whether a smoke extraction system has to be installed. The geometrical configuration is recommended to be included as well. A time constant is defined for the atrium with a certain design fire.