Casanova AO, López N, Gelen A, Guevara MV, Díaz O, Cimino L, D'Alessandro K, Melo JC. Radiat. Prot. Dosimetry 2004; 109(3): 189-195.

Affiliation

Instituto Superior de Tecnologías y Ciencias Aplicadas (InSTEC), Ave. Salvador Allende y Luaces, Quinta de los Molinos, Habana 10600, A.P. 6163, InSTEC, La Habana, Cuba. ocasanova@fctn.isctn.edu.cu

Copyright

(Copyright © 2004, Oxford University Press)

DOI

10.1093/rpd/nch326

PMID

15254322

Abstract

A cyclic electron accelerator Microtron MT-25 will be installed in Havana, Cuba. Electrons, neutrons and gamma radiation up to 25 MeV can be produced in the MT-25. A detailed shielding analysis for the bunker is carried out using two ways: the NCRP-51 Report and the Monte Carlo Method (MCNP-4C Code). The walls and ceiling thicknesses are estimated with dose constraints of 0.5 and 20 mSv y(-1), respectively, and an area occupancy factor of 1/16. Both results are compared and a preliminary bunker design is shown.