SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Hakkarainen T. J. Fire Sci. 2002; 20(2): 133-175.

Copyright

(Copyright © 2002, SAGE Publishing)

DOI

10.1177/0734904102020002074

PMID

unavailable

Abstract

A series of fire experiments was performed to study the gas temperature development and charring behaviour of timber construction compartments. The measured gas temperatures were 300-500 C lower than predicted by the parametric temperature-time curves of Eurocode 1 for unprotected and insufficiently protected timber structures. For structures protected with a double layer of gypsum plasterboard, the agreement was better. In all cases, however, the prediction was on the safe side. One protective layer of gypsum plasterboard delayed the onset of charring for 20 min. Using two layers, the delay time was doubled. Reduced charring rates for long exposure times were observed, resulting from the increasingly protective effect of the char layer withtime.


Language: en

NEW SEARCH


All SafetyLit records are available for automatic download to Zotero & Mendeley
Print