SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Nam S, Donovan LP, Kim JG. Fire Safety J. 2004; 39(3): 191-215.

Copyright

(Copyright © 2004, Elsevier Publishing)

DOI

unavailable

PMID

unavailable

Abstract

The current study has established a means of quantifying heat detectors' thermal response sensitivities through the use of plunge-tunnel tests, so that a fire safety engineer can estimate the detector response times with an acceptable accuracy. Eleven samples of fixed temperature-type detectors were chosen and the response times of the detector under varying test conditions were measured. An analyses of the collected data showed that response time index (RTI) provided the most consistent thermal sensitivity index throughout the different test conditions, among other possible candidates of the indices. In order to check the practical applicability of the RTI values assigned to each detector type, full-scale fire tests were conducted with heptane pan fires under a 3-m high ceiling. The matches between the measured and the estimated response times were excellent for all the detectors, except a "rate-compensated" high-temperature rating detector. Full-scale test results show that the RTI values, which were obtained through the bench-scale tests established with this study, will provide a very practical means of predicting detector-response times with an acceptable precision to fire safety engineers.

NEW SEARCH


All SafetyLit records are available for automatic download to Zotero & Mendeley
Print