Klingsch W. Fire Safety J. 1981; 4(4): 237-241.

Copyright

(Copyright © 1981, Elsevier Publishing)

DOI

unavailable

PMID

unavailable

Abstract

The resistance of massive steel columns is significantly better than for ordinary steel columns because of their much smaller aspect ratio. Under full service load they can attain a fire resistance of greater than 30 minutes for an ISO DIS 834 fire without any fire protection, and more than 90 minutes with a thin intumescent coating. Results of numerical thermal, and load bearing analysis, material investigations, and fire tests are summarized for practical application in fire engineering.