SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Chow WK. Fire Safety J. 1997; 28(2): 165-177.

Copyright

(Copyright © 1997, Elsevier Publishing)

DOI

unavailable

PMID

unavailable

Abstract

The time constant proposed to specify the smoke filling time in an atrium hall for design purposes is further evaluated in this paper using the plume expression fitted by dimensional analysis. The zone model FIRST developed at the Building and Fire Research Laboratory, NIST, U.S.A. is used to simulate the smoke filling time. Predicted results of the zone modelling simulation supported the fact that the time required to fill 80% of the atrium space with smoke is related to its time constant. Full-scale experimental results on smoke filling processes in atria available in the literature are used to justify this parameter. Use of this quantity to specify the smoke filling time for an atrium space is recommended with a selected design fire.