The aim of this study is to investigate the levels of electric and magnetic power frequency fields at 8 electrical transformation stations in the North-East counties of Romania and to check their compliance with standards. Spot measurements were carried out on both electric and magnetic fields under overhead conductors of 110-, 220- and 380-kV installations. The magnetic field levels were several orders of magnitude below the reference level for occupational exposure set by ICNIRP (International Commission on Non-Ionizing Radiation) or by Romanian regulations. In contrast, the electric field levels were about the same order of magnitude as the reference levels. In 2 electrical stations the reference level of 10 kV/m was exceeded at specific locations within the outdoor installations area. However, the additional reference level for short-time exposure included in Romanian regulations, 30 kV/m, was not exceeded.