Quintiere JG, Wang L. Fire Safety J. 2009; 44(5): 789-792.

Copyright

(Copyright © 2009, Elsevier Publishing)

DOI

10.1016/j.firesaf.2009.03.012

PMID

unavailable

Abstract

A new formula for fire-induced wall vent flow rate is developed based upon a theoretical derivation and mathematical fit to data. Previous research had developed a formula of mass flow rate for fire-induced doorway flows only. Here it is extended to include window flows. A theoretical model based on an ideal point source fire plume is used to guide the form of the empirical correlation. A thorough examination concerning the difference between the window and doorway flow modes is conducted. Both sill height and width of the windows pose key influence on the formula. The two vent configurations are merged into one equation. The results were compared to available flow data and shown to be within 15% accuracy for a wide range of fire conditions. Keywords: Compartment fire; Vent flows