TY - JOUR PY - 2002// TI - Evaluation of Exterior Insulation and Finish System Fire Hazard for Commercial Applications JO - Journal of fire protection engineering A1 - Alpert, Ronald L. A1 - Davis, R. J. SP - 245 EP - 258 VL - 12 IS - 4 N2 - To judge existing fire test methods in use or those planned/proposed for use with exterior insulation and finish system (EIFS) products, a critical commercial/industrial accident scenario has been identified that involves storage adjacent to a building exterior having a 90-degrees corner. The heat flux environment expected in the assumed accident scenario, as determined from the FM Approvals 50-ft. (15.25-m) Corner Test, is not reproduced by existing EIFS test methods, since these mostly involve flames issuing from a window opening. In the current study, the experience gained from testing two EIFS products in the 50-ft. corner has allowed practical procedures for the categorization of EIFS products to be recommended.

LA - SN - 1042-3915 UR - http://dx.doi.org/10.1106/1042391031317 ID - ref1 ER -