TY - JOUR PY - 1998// TI - Limitations of water mist as a total flooding agent JO - Journal of fire protection engineering A1 - Andersson, Petra A1 - Holmstedt, Göran SP - 31 EP - 50 VL - 9 IS - 4 N2 - The limitations of water mist in acting as a total flooding agent are discussed in this paper. The paper focuses on water mist consisting of droplets 1-100 μm in diameter. Water mists are very efficient as an extinguishing media if they are present in the flame. There are, however, several problems associated with introducing the water mist into the flame: the spray reaches only a short distance; small water droplets have a very short lifetime; droplets coagulate into larger droplets; large droplets hit obstacles such as walls and therefore have difficulties in being dispersed throughout the protected volume.
Language: en
LA - en SN - 1042-3915 UR - http://dx.doi.org/10.1177/104239159800900404 ID - ref1 ER -