TY - JOUR PY - 2001// TI - Simulation on natural smoke filling in atrium with a balcony spill plume JO - Journal of fire sciences A1 - Chow, W. K. A1 - Li, J. SP - 258 EP - 283 VL - 19 IS - 4 N2 - The smoke-filling process in atria of local shopping malls was studied. The scenario of smoke spreading from a shop located adjacent to an atrium was considered. A two-layer zone model, CL-Atrium, was developed with balcony spill plume. Three plume expressions due to Thomas et al. [13], Poreh et al. [12] and NFPA-92B [11] were used and assessed. Comparison was made with simulations due to CFAST. It is found that a condition has to be satisfied for the plume expression due to Thomas et al. [13]. Further, the results on the smoke layer temperature and interface height in the atrium are similar while using the plume expressions by Poreh et al. [12] and Thomas et al. [13].
Language: en
LA - en SN - 0734-9041 UR - http://dx.doi.org/10.1106/65LF-H4GA-9EW6-QF8E ID - ref1 ER -