%0 Journal Article
%T Stairwell Flow Pressurization -- A New Method
%J Journal of fire protection engineering
%D 2003
%A Jensen, L.
%V 13
%N 4
%P 251-274
%X Pressurization is used to prevent smoke spread into a stairwell. The stairwell height is limited by the pressure to open doors, about 80 Pa, the pressure to prevent smoke spread, about 20 Pa and the outdoor-indoor temperature-induced pressure gradient, about 2 Pa/m. This limits the height to 30m ((80 20)/2). However, this limit can be increased by balancing the temperature-induced pressure gradient with an equal and opposite flow pressure gradient created by a flow passing through the whole stairwell.<p />
%G 
%I SAGE Publishing
%@ 1042-3915
%U http://dx.doi.org/10.1177/1042391503035524