@article{ref1,
title="Stairwell Flow Pressurization -- A New Method",
journal="Journal of fire protection engineering",
year="2003",
author="Jensen, L.",
volume="13",
number="4",
pages="251-274",
abstract="Pressurization is used to prevent smoke spread into a stairwell. The stairwell height is limited by the pressure to open doors, about 80 Pa, the pressure to prevent smoke spread, about 20 Pa and the outdoor-indoor temperature-induced pressure gradient, about 2 Pa/m. This limits the height to 30m ((80 20)/2). However, this limit can be increased by balancing the temperature-induced pressure gradient with an equal and opposite flow pressure gradient created by a flow passing through the whole stairwell.<p />",
language="",
issn="1042-3915",
doi="10.1177/1042391503035524",
url="http://dx.doi.org/10.1177/1042391503035524"
}