@article{ref1,
title="Evaluation of Exterior Insulation and Finish System Fire Hazard for Commercial Applications",
journal="Journal of fire protection engineering",
year="2002",
author="Alpert, Ronald L. and Davis, R. J.",
volume="12",
number="4",
pages="245-258",
abstract="To judge existing fire test methods in use or those planned/proposed for use with exterior insulation and finish system (EIFS) products, a critical commercial/industrial accident scenario has been identified that involves storage adjacent to a building exterior having a 90-degrees corner. The heat flux environment expected in the assumed accident scenario, as determined from the FM Approvals 50-ft. (15.25-m) Corner Test, is not reproduced by existing EIFS test methods, since these mostly involve flames issuing from a window opening. In the current study, the experience gained from testing two EIFS products in the 50-ft. corner has allowed practical procedures for the categorization of EIFS products to be recommended.<p />",
language="",
issn="1042-3915",
doi="10.1106/1042391031317",
url="http://dx.doi.org/10.1106/1042391031317"
}