title="Simulation on natural smoke filling in atrium with a balcony spill plume",
journal="Journal of fire sciences",
year="2001",
author="Chow, W. K. and Li, J.",
volume="19",
number="4",
pages="258-283",
abstract="The smoke-filling process in atria of local shopping malls was studied. The scenario of smoke spreading from a shop located adjacent to an atrium was considered. A two-layer zone model, CL-Atrium, was developed with balcony spill plume. Three plume expressions due to Thomas et al. [13], Poreh et al. [12] and NFPA-92B [11] were used and assessed. Comparison was made with simulations due to CFAST. It is found that a condition has to be satisfied for the plume expression due to Thomas et al. [13]. Further, the results on the smoke layer temperature and interface height in the atrium are similar while using the plume expressions by Poreh et al. [12] and Thomas et al. [13].<p /><p>Language: en</p>",