@article{ref1,
title="The hazards of bulk oxygen delivery systems",
journal="Lancet",
year="1975",
author="Feeley, Thomas W. and McClelland, K. J. and Malhotra, I. V.",
volume="1",
number="7922",
pages="1416-1416",
abstract="Many hospitals throughout the world obtain oxygen from a supply of bulk liquid oxygen which is delivered throughout the hospital via pipelines. An incident in which, through a series of malfunctions, dangerously high pressure developed in the hospital oxygen pipeline is described. The oxygen delivery systen described lacked a relief valve to vent excessive pressures. In North America such a relief valve is required on all oxygen delivery systems. An alarm system is also required which detects rises in pipeline pressures. Regulations in the U.K. do not provide for pressure-relief valves on liquid oxygen pipeline systems. In the U.K. there is also no regulation on alarms to warn of high pipeline pressures. High-pressure accidents are a real threat to patients and hospital staff unless proper safeguards are built into oxygen delivery systems.  Keywords: Pipeline transportation<p /> <p>Language: en</p>",
language="en",
issn="0140-6736",
doi="",
url="http://dx.doi.org/"
}